Kontron NSC2U IP Network Server Manual do Utilizador Página 49

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 48
Kontron IP Network Server NSC2U
December 2009 Product Guide, rev. 1.4
49
Server Component Installations and Upgrades—NSC2U Server
Ventilation — The equipment rack must provide sufficient airflow to the front of the
server to maintain proper cooling. It must also include ventilation sufficient to exhaust
a maximum of 1200 BTU per hour for a fully loaded server system using the IP Network
Server NSC2U.
It is important to note that this measurement is the maximum, and a minimum or
typical system could use much less. You may want to calculate the BTU/hour
measurement more accurately for your configuration. An extra 500 BTU/hour over
many systems would translate into a large error calculating air conditioning capacity.
Vista de página 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 151 152

Comentários a estes Manuais

Sem comentários