Operating Instructions Chassis Monitoring Module (CP3-CMM1)
31.01.2003 10
♦ Alarm messages:
X = 0: No output of the alarm message
X = 1: Output of the alarm message
Address 50
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
fix 0000
Alarm OUT0
x
Alarm OUT1
x
Alarm OUT2
x
Alarm OUT3
x
Sum: 0000xxxx
Default:
(Decimal 127)
00001111
Address 51
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
fix 0 0
Alarm OUT4
x
Alarm OUT5
x
Alarm OUT6
x
Alarm OUT7
x
Alarm OUT8
x
Alarm OUT9
x
Sum: 00xxxxxx
Default:
(Default xxx)
00111111
♦ Conjunction of Input parameters with digital outputs
The input parameters can individually be assigned to the 10 digital outputs. If more than one input parameter is
assigned to an output, the inputs are logically OR-wired to the output.
Bit =1: Input parameter assigned to output
Bit =0: Input not assigned to output
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Ouput
Input parameters
nc
nc
V6 (-24V) out of tolerance
V5 (-12V) out of tolerance
V4 (+24V) out of tolerance
V3 (+12V) out of tolerance
V2 (+5V) out of tolerance
V1 (+3.3V) out of tolerance
nc
FCM-Auxiliary
FCM-TempFail
FCM-FanFail
DIN14 OR DIN15 / AC-fail_1 OR AC-fail_2
SYSRESET aktive
Temperaturr Threshold 1
Temperature Threshold 2
Broken wire of Temp. Sensor
DIN0 / SYSFAIL_in
DIN3 OR DIN4 / DEG_in_3 OR DEG_in_4
DIN1 OR DIN2 / DEG_in_1 OR DEG_in_2
DIN8 / FAL_in_4
DIN7 / FAL_in_3
DIN6 / FAL_in_2
DIN5 / FAL_in_1
OUT0 000000000000000010000000
Address 19 Address 18 Address 17
OUT1 000000000000001100000000
Address 22 Address 21 Address 20
OUT2 000000000010000000000000
Address 25 Address 24 Address 23
OUT3 000000000001000000000000
Address 28 Address 27 Address 26
OUT4 000000000000100000000000
Address 31 Address 30 Address 29
OUT5 000000000000000001000000
Address 34 Address 33 Address 32
OUT6 000010000000000000000000
Address 37 Address 36 Address 35
OUT7 001000000000000000000000
Address 40 Address 39 Address 38
OUT8 000000000000000000110000
Address 43 Address 42 Address 41
OUT9 000000000000000000001111
Address 46 Address 45 Address 44
Remark: The table shows the CMM default conjunction of input parameters to digital outputs